Gas Point
H2S, CO, NH3, HCN, NO2, SO2, O2, Cl2
Combustibles (Catalytic 0-100% LEL) or
Combustibles (IR 0-100% LEL)
One Transmitter
with interchangeable
electrochemical, infrared
and catalytic plug-in sensors
FEATURES: Fixed Gas Monitoring Systems
The GasPoint transmitter provides a 4-20 mA output signal that can be
connected to any control system (DCS, PLC, etc.). With advanced sensor
technology and microcontroller based operation, the GasPoint provides
continuous monitoring of hazardous gases.
- The GasPoint transmitter can accept any GasPoint sensor type : electrochemical, catalytic or IR (infrared). All plug-in sensor assemblies are fi eld-interchangeable.
- Full function sensor integrity test (auto) continuously advises gas
sensing ability and life ended. - Non-intrusive, one-person calibration with auto zero and auto span.
- Equipped with three 5-amp relay contacts—two gas alarm relays (low/high) and fault alarm. Field-selectable normally energized / de-energized and latching/non-latching alarm relay functions.
- Two backlit alphanumeric LCDs advise all environmental and gas
hazard conditions as well as instrument and sensor status. - Remote toxic/oxygen sensors can be installed over 3,900 ft./ 1,100 m
away; combustible sensors over 1,550 ft./475 m. Kit can be installed at any time. - Alarm setpoints displayed on demand—simply press the external button.
- Field programmable alarm levels.
- Backlight (auto) in low light conditions and alarm.
- Extensive fault diagnostics.
- 2-way digital communication using MODBUS module.